Regulation: Steady-state ±S% from no load to full load over the specified input voltage, frequency, and ambient temperature ranges.Operating Temperature: 0° C to +50° C (+32° F to +122° F).Circuit Protection: Refer to rectifier specifications for recommended external fusing.800 amp models have one set of contacts for rectifier failure alarms and signals for end cell switch inhibit, high voltage shutdown alarm and low current alarms. They also offer vital system alarms with LED indicators for power on, low current, high voltage, low voltage and fuse failure. Voltmeter reads zero when the rectifier is turned off. The units have full metering with ☒% output voltmeter and ammeter for monitoring rectifier operation.
Performance is assured with Marconi produced transformers, gold printed circuit board contacts to resist oxidation and specially rated filter capacitors that last four times longer than standard capacitors. 48V| 800 Amp Simple Type: Rectifier The Lorain RHM rectifier is available in an 800 amp model to provide regulated power and high operating efficiencies in a -48 volt system.